A comprehensive guide to the selection and technical parameters of dry-type transformers: 10 key points that engineers and procurement are most likely to overlook

In practical projects, the problem of selecting the wrong model for dry-type transformers is very common.

The capacity is sufficient, but the temperature rise exceeds the standard;
Voltage matching, but noise is not qualified;
Parameter compliance, but overseas acceptance failed.

This article will delve into the most critical but easily overlooked technical details of dry-type transformers from the perspective of engineering selection.

dry-type transformers
dry-type transformers

1.Capacity selection: You cannot just look at kVA

1.1 Continuous load and intermittent load

Dry-type transformers are highly sensitive to ambient temperature and require appropriate derating in the following scenarios:

  • high altitude
  • high temperature environment
  • Closed computer room

1.2 Overload Capacity Assessment

The short-term overload capacity of epoxy cast dry-type transformers is significantly weaker than that of oil immersed transformers, and the load curve needs to be evaluated in advance.

2.Voltage level and wiring group

Common combinations:

  • 10кВ / 0.4кВ
  • 20кВ / 0.4кВ

The wiring group should match the system protection logic, such as:

  • Дин11
  • Yyn0

3.Insulation level and temperature rise design

Класс изоляцииTypical Temperature Rise
Класс F100K
Класс Н125K

When choosing, consider long-term operating temperature rather than short-term limits.

4.Selection of cooling method

АН: Естественное охлаждение, низкий уровень шума
ИЗ: Forced air cooling, capacity can be increased by 30-40%

But the reliability and maintenance of the fan also need to be taken into consideration.

5.Partial discharge level

High quality dry-type transformers typically require:

  • Partial discharge ≤ 10 pC

This is one of the core indicators for overseas project acceptance.

6.Noise control

Noise often becomes a veto in data center and commercial building projects.
Attention should be paid to:

  • core structure
  • Shock absorption design
  • Installation foundation

7.Protection level and environmental adaptability

Common levels:

  • IP00 (indoor)
  • IP23/IP31 (anti drip, anti foreign object)

8.Energy efficiency and loss indicators

Critical loss parameters:

  • no-load loss
  • load loss

The EU and North American markets have particularly strict requirements for this.

9.Standards, certifications, and documents

Common requirements:

  • МЭК / IEEE
  • CE
  • ISO system documents

10Hidden risks of export projects

Wooden crate packaging standard
Shipping moisture prevention
Technical document language

Dry-type transformers are not necessarilythe better the parameter table, the safer it is”, but rather highly coupled system equipment with application scenarios.
The truly professional selection is a comprehensive reflection of technical understanding, engineering experience, and standard awareness.

Лоянская компания Datang Energy Technology Co., ООО. это высокотехнологичное предприятие, интегрирующее R&Д, производство и поставка силового оборудования, такого как трансформаторы, новые энергетические компоненты, распределительные шкафы и инверторы. С технологическими инновациями в основе, мы фокусируемся на создании высоконадежных и высокопроизводительных решений в области электропитания для обслуживания клиентов по всему миру.. Со строгой системой контроля качества и сертификацией международного стандарта., мы продолжаем выпускать превосходную продукцию и даем возможность клиентам создавать безопасные и стабильные энергосистемы..